- Overview
- Technical data
- Accessories
- Certification
- Business data
- Download
Product advantages
☑ The analog input module can receive standard signals of 0-20mA and 4-20mA.☑ 8-channel analog input, current type.
☑ Two LED indicators indicate that the module is operating normally and communication is normal.
☑ Each input channel comes with an LED indicator light.
☑ Magnetic isolation between the on-site layer and the system layer.
☑ Transmit in 16 bit resolution.
☑ Protection level IP20.
3D model
Technical Information
Current measurement range | 0-20mA, 4-20mA |
System feed current | <120mA |
Reverse circuit protection | Yes |
Error diagnosis | Yes |
Working voltage | 24V DC+20%/-15% |
Current input accuracy (full temperature range) | ± 0.2% (full range) |
Diagnostic reporting function configuration | Support |
Line type | 2/3/4 wire system |
Number of channels | 8 |
Data size | 16 Byte |
Resolving power | 16bit |
Signal type | Single ended |
Conversion time | 60us/channel |
Isolation method | Magnetic isolation from the on-site layer |
Filtering time | Configurable |
Environmental requirements
Protection type | IP20 |
working temperature | -25... 60 ℃ |
Storage temperature | -40... 85 ℃ |
relative humidity | 5... 95% RH (condensation) |
Wiring parameters
The maximum crimping area of the wire | 1.5mm² |
0.14mm² | |
Maximum crimping area of wire (AWG) | AWG16 |
Connection technology: input/output | PUSH-IN type terminal blocks |
Strip length | 8-10mm |
Installation method | DIN-35 type guide rail |
Order number | 30050002657 |
Packing unit | 1 |
Minimum order quantity | 1 |
Products weight (without packaging) | 60g |