- Overview
- Technical data
- Accessories
- Certification
- Business data
- Download
Product advantages
☑ PROFINET bus communication protocol.☑ Integrated power module.
☑ LED displays the operating status, providing alarm information and bus faults.
☑ Dual PROFINET connection (RJ45,10/100Mbps).
☑ Adhere to the characteristics of MRP media redundancy protocol ring.
☑ Protection level IP20.
3D model
Technical Information
Transmission speed | 10/100Mbps, full duplex |
Characteristic | RT, compliant with Class C, MRP, automatic addressing/topology detection |
Alarm function | Diagnostic alarm, process alarm, connector plugging alarm |
Minimum cycle time | 1ms |
Internal system electrical terminal rated voltage input | 24V DC (20.4V DC~28.8V DC) |
Internal system electrical terminal rated current input | 0.75A (typical value at 24V) |
Internal system electrical rated voltage output | 5VDC |
Internal system electrical rated current output | 2A |
Working voltage | 24V DC+20%/-15% |
Communication protocol | PROFINET-RT |
Number of expandable modules | Thirty-two |
Transmission distance | 100米 |
PDO data | 1024 bytes |
Transmission medium | Category 5 twisted pair cables |
Isolation method | Electrical isolation from the site |
Bus address setting | PROFINET specification |
Environmental requirements
Permissible ambient temperature (during operation) | -25-60 ℃ |
Permissible ambient temperature (storage) | -40-85 ℃ |
Protection type | IP20 |
Pollution level | 2. Comply with IEC 61131-2 standard |
Working altitude | Temperature without derating: 0-2000m |
Relative humidity (non condensing) | 5-95% RH |
Anti vibration | 4g, in accordance with IEC 60068-2-6 standard |
Impact resistance | 15g, in accordance with IEC 60068-2-27 standard |
EMC - Immunity | Complies with EN 61000-6-2 standard |
EMC - Radiated interference | Complies with EN 61000-6-3 standard |
Corrosion resistance | Complies with IEC 60068-2-42 and IEC 60068-2-43 standards |
Permissible H2S pollutant concentration at 75% relative humidity | 10ppm |
Permissible SO2 pollutant concentration at 75% relative humidity | 25ppm |
Wiring parameters
Connection technology: input/output | PUSH-IN type terminal blocks |
Crimping area of wire | 0.2~1.5mm²/26~16AWG |
Strip length | 8-10mm |
Order number | 30050002548 |
Packing unit | 1 |
Minimum order quantity | 1 |
Products weight (without packaging) | 200g |