- Overview
- Technical data
- Accessories
- Certification
- Business data
- Download
Product advantages
☑ TUV☑ Safety switch, DO signal input
☑ 3NO+1NC
3D model
Input
Current consumption | ≤ 90mA |
Test pulse width | ≤3ms |
Test pulse period | 100ms |
Cable resistance | ≤ 15Ω |
Input devices | Safety switch, DO signal |
Output
Signal type | 3NO + 1NC |
Contact type | Forced guided |
Contact material | AgSnO2+0.2μmAu |
Contact loading | AC-15: 5A/230V, DC-13:5A/24V |
Contact fuse protection | 10A gL/gG(NO), 6A gL/gG(NC) |
Times
Switch-on | ≤200ms |
Release | ≤50ms |
Switching frequency | ≤4Hz |
Environmental
EMC | IEC/EN60947,IEC61326-3-1,IEC/EN61000-6-2,IEC/EN61000-6-4 |
Rated insulation voltage | 250V AC |
Rated impulse voltage | 6000V(1.2/50μs) |
Dielectric strength | 1500V AC, 1min |
Clearance and creepage | IEC60947-1 |
Vibration | 10Hz ~ 55Hz, 0.35mm |
Overvoltage category | III |
Pollution degree | 2 |
Protection type | IP20 |
Ambient temperature | -20°C~ +60°C |
Storage temperature | -40°C~ +80°C |
Relative humidity | 10 %RH ~ 90 %RH(40 ℃) |
Atmosphere pressure | 80kPa~106kPa |
Operating altitude | ≤ 2000m |
Mechanical
Mechanical life | 10000000 cycles |
Connect type | Screw terminal |
Weight | 180g |
Safety Values
Performance level | PLe,ISO13849 |
Category | Cat.4,ISO13849 |
DTI | ISO13849 |
PTI | 20 Years,ISO13849 |
DC | 99%,ISO13849 |
MTTF | 164 Years,ISO13849 |
CCF | 68,ISO13849 |
SIL | SIL3,IEC61508 |
SIL CL | SILCL3,IEC62061 |
HFT | 1,IEC62061 |
SFF | ≥99%,IEC62061 |
DC (AVG)/PTI = 20 years | IEC62061 |
PFH | IEC62061 |
Stop Category | 0,IEC60204 |
Power supply
Voltage range | 20V~32V DC(Typ.24V) |
Power supply type | Loop supply |
Power dissipation | ≤ 2.2W/24V DC |
Order number | 30010000262 |
Packing unit | 1 |
Minimum order quantity | 1 |
Products weight (without packaging) | 180 |
User Manual | |
---|---|